This paper presents the design of tie line tripping and load shedding for a large customer system with multiple cogeneration units. The mathematical models with the corresponding parameters of cogenerators, governors, exciters and the equivalent generation unit to represent the external utility power system have been identified. The critical clearing time has been solved by performing the transient stability analysis for the tie line tripping of the industrial power system under various contingencies of the utility network. To enhance the system stability, the protective scheme by including the directional over current relay, under voltage relay and under frequency relay with proper settings has been applied. By this manner, the industrial power system is able to be isolated from the utility system in time to prevent the collapse of the industrial power system and the cogeneration units. To restore the system frequency to the normal operation condition, the load shedding is considered by both frequency deviation and frequency change rate for each load shedding step. The computer simulation of the industrial power system has verified the effectiveness of the proposed protective strategy.
机译:本文介绍了具有多个热电联产单位的大客户系统的扎线跳闸和负载脱落。已经识别了具有相应参数的新电生物器,调速器,励磁器和等效产生单元的数学模型已经识别出代表外部公用电力系统。通过在公用事业网络的各种突发事件下对工业电力系统的连接线跳闸进行瞬态稳定性分析来解决了关键清算时间。为了增强系统稳定性,通过包括在电压继电器下方和具有适当设置的电压继电器下方和频率继电器下的方向上继电器的保护方案。通过这种方式,工业电力系统能够及时与公用事业系统隔离,以防止工业电力系统和热电联产单位的崩溃。为了将系统频率恢复到正常操作条件,通过频率偏差和每个负载缩小步骤的频率偏差和频率变化率考虑负载脱落。工业电力系统的计算机仿真验证了提出的保护策略的有效性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号