Laboratory and on-site measurements of TEV generated by disconnector switching in 362 kV GIS

机译:362 kV GIS中通过隔离开关切换产生的TEV的实验室和现场测量

获取原文

摘要

The special resistor characteristic impedance divider recommended in IEC 1321-1 was designed to measure the transient enclosure voltage (TEV) induced by DS switching in 362 kV GIS both in laboratory and on-site. The characteristics of such a measuring system were studied and the optimal parameters were determined through the unit step response method. The test results showed that the amplitudes of TEV were of normal distribution and the maximum probability was about 40% appearing when TEV amplitude was around 800 V. The high frequency component measured was up to 40 MHz.
机译:IEC 1321-1中推荐的特殊电阻器特性阻抗分压器旨在测量在实验室和现场在362 kV GIS中DS切换引起的瞬态外壳电压(TEV)。研究了这种测量系统的特性,并通过单位阶跃响应法确定了最佳参数。测试结果表明,TEV幅值呈正态分布,当TEV幅值约为800 V时,出现的最大概率约为40%。测得的高频分量高达40 MHz。