首页> 外文会议>Electrical Insulation and Dielectric Phenomena, 1998. Annual Report. Conference on >Insulation deterioration of a 66 kV line-post insulator covered with salt-ice
【24h】

Insulation deterioration of a 66 kV line-post insulator covered with salt-ice

机译:覆盖有盐冰的66 kV线后绝缘子的绝缘性能下降

获取原文

摘要

In order to study the insulation deterioration and flashover performance of transmission-line insulators in seasalt and freezing weather, measurements of DC leakage resistance and flashover tests were carried out in a cold room. These experimental results of comparison between DC leakage resistance and flashover events show that R1 higher or lower than 1/spl times/10/sup 4/ /spl Omega/ has a higher probability of flashover occurrence.
机译:为了研究在海盐和寒冷天气下输电线路绝缘子的绝缘性能恶化和闪络性能,在寒冷的房间中进行了直流泄漏电阻的测量和闪络测试。这些直流泄漏电阻与闪络事件之间比较的实验结果表明,R1高于或低于1 / spl次/ 10 / sup 4 / / splΩ/时具有更高的发生闪络的可能性。