Performance improvement of 33 kV line-post insulators in harsh environment

机译:33 kV线柱绝缘子在恶劣环境下的性能改进

获取原文
获取原文并翻译 | 示例
           

摘要

Comprehensive standard tests were conducted on 33 kV line-post porcelain insulators in order to improve their performance in harsh environment in comparison to the newly introduced polymeric ones. These tests are the lightning impulse withstand and flashover tests, and the AC artificial pollution tests. The latter were conducted in a salt-fog chamber. Silicone rubber insulators showed superior performance than adding heat-shrinkable and wraparound creepage extenders to the existing line-post porcelain insulators or using new polymeric insulators.
机译:与新引入的聚合物绝缘子相比,在33 kV线路支柱瓷绝缘子上进行了全面的标准测试,以提高其在恶劣环境下的性能。这些测试是雷电冲击承受能力和闪络测试,以及交流人工污染测试。后者在盐雾室中进行。与在现有的线柱式瓷绝缘子中添加可热收缩和环绕爬电的增量剂或使用新的聚合物绝缘子相比,硅橡胶绝缘子表现出卓越的性能。