首页> 外文会议>International symposium on heating, ventilating and air conditioning >REASON AND SOLUTION OF UNSATISFIED PARAMETERS IN HIGH-BAY DEPOT AND MOISTURE CONDENSATION IN CONNECTED EXTERNAL CORRIDOR IN A CIGARETTE FACTORY
【24h】

REASON AND SOLUTION OF UNSATISFIED PARAMETERS IN HIGH-BAY DEPOT AND MOISTURE CONDENSATION IN CONNECTED EXTERNAL CORRIDOR IN A CIGARETTE FACTORY

机译:卷烟工厂连接外走廊中的高湾仓库和水分凝固的原因及解

获取原文

摘要

In winter the indoor temperature and humidity cannot be satisfied in high-bay depot and moisture condensation exists in external corridor connected to the depot in a cigarette factory. Through site test and numerical analysis, it is deduced that two stock entrances at 10m height cause part of supply air bypassing to the connected external corridor from upper space of the high-bay depot, which results in both of the above problems. Then a retrofit scheme by adding two small chambers at each end of the corridor is proposed. In the chamber which is closer to the depot, perforated ceiling air supply is designed to resist the bypassing air. Further simulation result shows that the air flow between the high-bay depot and the corridor can be effectively cut off and the existing problems can be solved. The results can provide some references to similar air flow distribution design and retrofit.
机译:在冬季,在高湾仓库中,在高湾仓库中不能满足室内温度和湿度,并在卷烟工厂连接到储库的外部走廊中存在水分冷凝。通过现场测试和数值分析,推导出10米高的两个股票入口,导致部分供应空气从高湾仓库的上层旁路旁路,导致上述两个问题。然后,提出了通过在走廊的每个端部添加两个小腔室来改造方案。在更靠近仓库的腔室中,穿孔吊顶空气供应设计以抵抗旁路空气。进一步的仿真结果表明,可以有效地切断高海湾仓库和走廊之间的空气流动,并且可以解决现有的问题。结果可以提供对类似气流分布设计和改造的一些引用。