首页> 外文会议>Iranian Conference on Electrical Engineering >Characteristic Impedance of Stator Bars to Study Partial Discharge Pulse Propagation in Generators
【24h】

Characteristic Impedance of Stator Bars to Study Partial Discharge Pulse Propagation in Generators

机译:定子条的特性阻抗研究发电机中的局部放电脉冲传播

获取原文

摘要

Partial discharge (PD) test is one of the most commonly used methods for monitoring the status of generator insulation system. Despite the major use of this method, the interpretation of its results faces many challenges. Therefore, it is necessary to study and recognize the PD pulse propagation process in the stator winding. In this study, the characteristic impedance of a generator bar is calculated to increase the accuracy of modeling the stator winding. Depending on how the bar positioned in the stator core, the characteristic impedances of the slot part and the end winding are obtained using finite element method. Finally, based on the results obtained, a suitable model for PD pulse propagation is implemented in EMTP software to compare the simulation results with the previous experimental studies.
机译:局部放电(PD)测试是监视发电机绝缘系统状态的最常用方法之一。尽管主要使用此方法,但其结果的解释仍面临许多挑战。因此,有必要研究和认识定子绕组中PD脉冲的传播过程。在这项研究中,计算了发电机条的特征阻抗,以提高对定子绕组建模的准确性。根据条在定子芯中的定位方式,使用有限元方法获得槽部和端部绕组的特征阻抗。最后,基于获得的结果,在EMTP软件中实现了适合PD脉冲传播的模型,以将仿真结果与先前的实验研究进行比较。