Dependence of Over-Voltage Level of Different Voltage Class Surge Arrestors on Grounding Device Papameters. Experimental Study and Simulation

机译:不同电压类浪涌避雷器对接地装置参数的依赖性。实验研究与仿真

获取原文

摘要

It is demonstrated experimentally at surge protecting device connection to grounding system overvoltage limitation level depends on inductive part of the grounding impedance. Experimental study of resistive-inductive equivalent circuit parameters effect has shown presence of high frequency voltage component with characteristic period 1-3 μs. Depending on the grounding inductance the overvoltage limitation level rises up to 20-40%/. It can substantially reduce the protected equipment life time.
机译:在实验上通过实验证明,在浪涌保护装置连接到接地系统过电压限制水平取决于接地阻抗的感应部分。电阻电感等效电路参数效应的实验研究表明,具有特性周期1-3μs的高频电压分量的存在。根据接地电感的不同,过电压限制级别上升至20-40%/。它可以大大减少受保护的设备寿命。