摘要

For high-speed computer systems, the high-power devices such as Central Processor Units (CPUs) and Graphics Processing Units (GPUs) generally must be arranged close together to reduce electrical channel routing distances. In such cases water cooling enables greater device density than that achievable with air cooling. In contrast to typical implementations that utilize a separate coldplate for each high-power device, we use a single flexible coldplate to cool multiple devices. The flexibility allows the single coldplate to adapt to varying device heights and/or tilts. We solder or braze the perimeters of two thin, concave metal sheets to form a coldplate chamber. Cooling fin packs inside the chamber are soldered or brazed to internal chamber walls. Careful control of this metal-to-metal interface is required to minimize voiding and achieve good thermal contact. Under the fin packs the external chamber wall contacts the heat generating devices through a thermal interface material (TIM). In the regions between devices, the thin walls of the empty cavity provide mechanical flexibility. This allows for device height variation while maintaining full contact through a thin TIM. Having a single coldplate reduces both cost and potential water leakage at attachment junctions.
机译:对于高速计算机系统,通常必须将诸如中央处理器(CPU)和图形处理单元(GPU)之类的大功率设备靠近放置,以减少电气通道的布线距离。在这种情况下,水冷比空冷可实现更大的设备密度。与为每个大功率设备使用单独的冷却板的典型实现方式相反,我们使用单个柔性冷却板来冷却多个设备。灵活性允许单个冷却板适应不同的设备高度和/或倾斜度。我们将两块凹入的薄金属板的周边焊接或铜焊,以形成冷板室。腔室内的散热片组被焊接或铜焊到腔室内壁上。需要对此金属与金属的界面进行仔细控制,以最大程度地减少空隙并实现良好的热接触。在鳍片组的下方,外腔室壁通过热界面材料(TIM)与生热设备接触。在设备之间的区域中,空腔的薄壁提供了机械柔韧性。这允许器件高度变化,同时通过薄的TIM保持完全接触。拥有单个冷却板既可以降低成本,又可以减少附件连接处的漏水现象。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号