In the event of an earth fault in one of the two systems of a three-winding transformer, an increase in the star-point voltage occurs in the disturbed system. This voltage is transferred to the undisturbed systems due to capacitive coupling, to affected earth faulty system and to earth. As a result, three phase voltages to earth are different in magnitude and phase position compared to their undisturbed service status. In this paper the mesh analysis method is used to calculate the neutral point shift of the faulted winding necessary to obtain values of transferred voltages to the unaffected winding (the one which is not earth faulted). The results are analyzed to investigate the influence of winding and network neutral grounding (insulated, solidly grounded, grounded over impedance) on the results.
机译:在三个绕组变压器的两个系统中的一个中的接地故障的情况下,在受干扰的系统中发生星点电压的增加。由于电容耦合,该电压转移到未受干扰的系统,以影响地球故障系统和地球。结果,与其未受干扰的服务状态相比,地面的三个相电压在幅度和相位位置不同。在本文中,网状分析方法用于计算所需的断层绕组的中性点偏移,以获得转移电压的值,以获得未受影响的绕组(不是接地故障的)。分析结果以研究绕组和网络中性接地的影响(绝缘,稳定接地,接地的阻抗)。