Fault Analysis of 220kV High Voltage Circuit Breaker

机译:220kV高压断路器的故障分析

获取原文

摘要

As the switch and protection equipment of power system, the reliable work of high voltage circuit breaker is of great significance to the safe operation of the whole power system. Mechanical fault is still the main fault of high voltage circuit breaker. Timely and accurate diagnosis of mechanical fault of high voltage circuit breaker is the key to realize condition maintenance of high voltage circuit breaker and ensure safe operation of power grid. Related research has been paid more and more attention. This paper introduces a fault in which the three- phase closing time of the circuit breaker are not up to standard at the same time. Through field inspection, size measurement and fault simulation, it is clear that the cause of the fault is the interval characteristic, the two-wheel gap, and the exposed size of the closing spring rod is not up to standard. According to the specific causes of the fault, the corresponding investigation measures are put forward. Finally, the key and difficult problems in the field of mechanical fault diagnosis of high voltage circuit breakers are discussed and the development of diagnosis methods in the future is prospected.
机译:高压断路器作为电力系统的开关和保护设备,对整个电力系统的安全运行具有重要意义。机械故障仍然是高压断路器的主要故障。及时准确地诊断高压断路器的机械故障是实现高压断路器状态维护,确保电网安全运行的关键。相关研究受到越来越多的关注。本文介绍了一种故障,其中断路器的三相合闸时间未同时达到标准。通过现场检查,尺寸测量和故障模拟,很明显,故障原因是间隔特性,两轮间隙和闭合弹簧杆的裸露尺寸不符合标准。根据故障的具体原因,提出相应的调查措施。最后,讨论了高压断路器机械故障诊断领域中的关键和难点问题,并展望了未来诊断方法的发展。