首页> 外文会议>International Scientific Conference on Electric Power Engineering >Earth fault current distribution and proof method of global earthing systems
【24h】

Earth fault current distribution and proof method of global earthing systems

机译:全球接地系统接地故障电流分布及验证方法

获取原文

摘要

In order to estimate the currents as well as the relevant voltage drops in case of an earth fault, a calculation model was prepared to give an overview of possible dangerous earth potential rises, touch and step voltages. The combination of two inductively coupled loops and a low voltage model for an earth fault in a cable ring structure, which is made up from one single feeder operated with an open circuit breaker led to the calculation of the reduction factor. When inserting typical values for an urban low voltage network, it is shown that the earth fault current returns mainly through the cable sheaths and not via the grounding system of the afflicted ring main unit.
机译:为了估计接地故障时的电流以及相关的电压降,准备了一个计算模型以概述可能的危险地电位上升,接触电压和阶跃电压。电缆环结构中的两个电感耦合环路和一个接地故障的低电压模型的组合,是由一个带开路断路器的单个馈线组成的,从而可以计算出减小系数。当插入城市低压网络的典型值时,表明接地故障电流主要通过电缆护套返回,而不是通过患病环形主机的接地系统返回。