Earth fault current distribution and proof method of global earthing systems

机译:全球接地系统的接地故障电流分布及证明方法

获取原文

摘要

In order to estimate the currents as well as the relevant voltage drops in case of an earth fault, a calculation model was prepared to give an overview of possible dangerous earth potential rises, touch and step voltages. The combination of two inductively coupled loops and a low voltage model for an earth fault in a cable ring structure, which is made up from one single feeder operated with an open circuit breaker led to the calculation of the reduction factor. When inserting typical values for an urban low voltage network, it is shown that the earth fault current returns mainly through the cable sheaths and not via the grounding system of the afflicted ring main unit.
机译:为了估计接地故障的电流以及相关电压下降,准备了计算模型,以概述可能的危险地球电位升高,触摸和阶跃电压。两个电感耦合环的组合和电缆环结构中的接地故障的低电压模型,其由具有开路断路器操作的一个单个馈线构成的电缆环结构,导致减小因子的计算。当插入城市低压网络的典型值时,显示接地故障电流主要通过电缆护套返回,而不是通过受折磨环主单元的接地系统返回。