This paper discusses a transformerless hybrid active filter integrated into the 6.6-kV, 1-MW adjustable-speed motor drive having a three-phase diode rectifier at the front end. The hybrid filter consists of an active filter using a three-level diode-clamped PWM converter rated at 60 kVA, and a 250-kVA passive filter tuned to the 7th-harmonic frequency. They are directly connected in series without transformer. This circuit configuration enables to use 1.2-kV IGBTs because the dc voltage of the three-level converter is 1.32 kV (20% of 6.6 kV). Voltage-balancing control characterized by superimposing a 6th-harmonic zero-sequence voltage on the active-filter voltage reference in each phase is introduced to the three-level converter with triangle-carrier modulation. Experimental waveforms obtained from a 400-V 15-kW down-scaled system verify the viability and effectiveness of the proposed hybrid filter, keeping the two dc-capacitor voltages balanced well.
机译:本文讨论了集成到6.6 kV,1-MW可调速度电动机驱动中的无变压器混合动力有源滤波器,在前端具有三相二极管整流器。混合滤波器包括使用在60 kVA的三电平二极管钳位PWM转换器的有源滤波器,以及调谐到第7次谐波频率的250 kVA无源滤波器。它们直接串联无变压器。该电路配置可以使用1.2-KV IGBT,因为三级转换器的直流电压为1.32 kV(20%的6.6 kV)。通过在每个相中叠加在每个相位上的主动滤波器电压参考上叠加6次谐波零序电压的电压平衡控制被引入三级转换器,具有三角形载波调制。从400V 15-kW下缩放系统获得的实验波形验证了所提出的混合滤波器的可行性和有效性,使两个直流电容电压保持良好。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号