An electronic circuit in a control panel installed in a substation for Japanese bullet train (Shinkansen) was damaged due to a lightning. A field test is carried out to clarify the cause of the failure. The results show that a voltage is induced on a control cable for a earthing system and its amplitude exceeds the lightning withstand voltage of the control circuit. The effect of an earthing of an unused core in the control cable is investigated at a traction substation. To reduce the induced voltage, the unused core has to be earthed at the end of the control panel. If the core is earthed at the other side, a high voltage appears at the control panel. The effect of the lightning surge waveform on the induced voltage is also discussed. These results are effective for a proposal of a countermeasure to the fault and insulation design of traction substations.
机译:日本子弹头列车(新干线)变电站中安装的控制面板中的电子电路由于雷电而损坏。进行现场测试以查明故障原因。结果表明,在接地系统的控制电缆上感应出电压,其幅度超过了控制电路的耐雷电压。在牵引变电站研究了控制电缆中未使用的芯线接地的影响。为了降低感应电压,未使用的磁芯必须在控制面板的末端接地。如果芯线在另一侧接地,则控制面板上会出现高压。还讨论了雷电浪涌波形对感应电压的影响。这些结果对于提出牵引变电站的故障和绝缘设计对策的建议是有效的。