摘要

In this article, the characteristics of arching and voltage distribution between different fractures as well as over-voltage of capacitor bank is analyzed. The results show that when employing phase-control maneuver, if time dispersion of each fracture is limited in 1.5ms, re-strike can be avoided. The obtained results could help to propose the time dispersion requirement of each break model when using the scheme of series vacuum multi-break interrupting combining with phase-control maneuver.
机译:本文分析了不同裂缝之间的拱形和电压分布以及电容器组的过电压特性。结果表明,采用相控策略时,如果将各裂缝的时间分散控制在1.5ms以内,就可以避免重击。当采用串联真空多中断与相控策略相结合的方案时,所获得的结果将有助于提出每个中断模型的时间分散要求。