首页> 外文会议>IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems >Embedded two phase liquid cooling for increasing computational efficiency
【24h】

Embedded two phase liquid cooling for increasing computational efficiency

机译:嵌入式两相液体冷却可提高计算效率

获取原文

摘要

High-end server-class processors continue to push towards increased performance in both single thread and throughput performance. Improved computational performance and power efficiency can be achieved by increasing the number of complex cores through three-dimensional (3D) chip stacking technology. However, the thermal and associated reliability issues can be a limiting factor in such a strategy unless it is augmented by an aggressive, new cooling solution. This research paper demonstrates a novel intrachip two-phase liquid cooling technology with channel dimensions which are consistent with through silicon vias (TSV) compatible 3D chip stacking to mitigate any thermal constraints. To evaluate the benefits, data from characterization studies of IBM POWER7+™ systems and corresponding microprocessor power maps were used to generate power and computational performance models. These models were combined with system-level models to perform a quantitative analysis on system performance.
机译:高端服务器级处理器继续推动单线程和吞吐量性能的提高。通过使用三维(3D)芯片堆叠技术增加复杂内核的数量,可以提高计算性能和电源效率。但是,热和相关的可靠性问题可能是这种策略中的限制因素,除非通过积极的新型冷却解决方案加以补充。这篇研究论文演示了一种新颖的芯片内两相液体冷却技术,其通道尺寸与硅通孔(TSV)兼容的3D芯片堆叠相一致,从而减轻了任何热约束。为了评估收益,使用IBM POWER7 +™系统的特性研究数据和相应的微处理器功率图来生成功率和计算性能模型。这些模型与系统级模型结合在一起,可以对系统性能进行定量分析。