首页> 外文会议>International Conference on Industrial Engineering >Selective isolation continuous monitoring system in the networks of 6,10 kV
【24h】

Selective isolation continuous monitoring system in the networks of 6,10 kV

机译:6,10 kV网络中的选择性隔离连续监控系统

获取原文

摘要

The need for the isolation selective monitoring for networks with the isolated neutral of 6, 10 kV is shown. The lack of monitoring systems possessing selectivity of action is presently noted. A possibility of isolation selective control on the basis of regime parameters measurement in networks of 6, 10 kV, such as voltage and currents at the beginning and the end of the line, and also angles between them is proved. According to the regime parameters measurement for the most difficult case, the line with tap, the analytical dependences for determination of isolation conductivity concerning the earth is given. Errors of the network conductivity determination concerning the earth in case of lines with tap in it are analyzed. It is shown that at isolation conductivity determination of a network concerning the earth by the formulas offered the error won't exceed 10%. The increase of measurement accuracy can be provided with measurement of regime parameters at the beginning of the tap line.
机译:示出了对具有6,10kV的隔离中性的网络的隔离选择性监测。目前还注意到缺乏具有选择性选择性的监测系统。在6,10kV网络中的制度参数测量的基础上,在6,10kV的网络中测量的可能性,例如在线的开头和末端的电压和电流,并且它们之间的角度被证明在它们之间。根据最困难情况的制度测量值,给出了具有抽头的线,给出了用于确定地球的隔离电导率的分析依赖性。分析了与地球有关地球的网络电导率确定的误差。结果表明,在由提供的公式中,在提供有关地球的网络的隔离电导率确定时误差不会超过10%。测量精度的增加可以在抽头线开始时具有测量结果。

著录项