首页> 外文会议>Conference on Precision Electromagnetic Measurements >Experience with Current Transformer Calibration System Based on Rogowski Coil
【24h】

Experience with Current Transformer Calibration System Based on Rogowski Coil

机译:基于Rogowski线圈的电流变压器校准系统经验

获取原文

摘要

This paper discusses experience with current transformer calibration system based on the Rogowski coil. Rogowski coil has no ferromagnetic material in the core and thus the coil cannot be saturated. This means that the coil has inherently excellent linearity. It can be calibrated with low current using a current shunt. The system was taken into use in 2003. Stability of the system is demonstrated, and experience with using the coil is summarized. Proven overall uncertainty in routine calibration work is 0.0025 % for ratio error and 50 μrad for phase displacement up to 8 kA.
机译:本文讨论了基于Rogowski线圈的电流变压器校准系统的体验。 Rogowski线圈在芯中没有铁磁性材料,因此线圈不能饱和。这意味着线圈具有固有的优异线性度。使用电流分流器可以用低电流校准它。该系统于2003年被用途。概述了系统的稳定性,并且总结了使用线圈的经验。经过验证的常规校准工作中的总体不确定性为0.0025%,比率误差和50μr用于相位位移的50μg,高达8 ka。