Harmonic Mitigation of an Improved High Voltage Current Source for On-Site System Calibration of High Voltage Transformer Loss Measurement Systems

机译:高压变压器损耗测量系统现场系统校准改进的高压电流谐波的谐波缓解

获取原文

摘要

This paper proposes an open-loop technique that mitigates the harmonic distortion in high load currents for onsite system calibrations of high voltage transformer loss measurement systems. The harmonic distortion induced by the current transconductance amplifier and current injector poses high burden on the feedback current correction loop and thus may compromise the measurement accuracy. Accordingly, a harmonic mitigation technique is introduced through online system identification and open-loop anti-harmonic injection. This methodology significantly reduces the THD in the load current from 0.3% to less than 0.022%.
机译:本文提出了一种开环技术,可降低高负载电流的谐波失真,用于高压变压器损耗测量系统的现场系统校准。由电流跨导放大器和电流注射器引起的谐波失真对反馈电流校正环上的高负担,因此可能会损害测量精度。因此,通过在线系统识别和开环防谐注射引入谐波缓解技术。该方法显着降低了载荷电流的0.3%至小于0.022%的THD。