首页> 外文会议>Annual IEEE Applied Power Electronics Conference and Exposition >The Reactive Power Compensation and Harmonic Filtering and the Over-voltage Analysis of the ITER Power Supply System
【24h】

The Reactive Power Compensation and Harmonic Filtering and the Over-voltage Analysis of the ITER Power Supply System

机译:反应功率补偿和谐波滤波和迭代电源系统的过电压分析

获取原文

摘要

The ITER Coil Power Supply System is characterised by a very large AC/DC conversion plant which produces a relatively high amount of reactive power and harmonic currents. Consequently, the ITER power supply system will include substantial reactive power compensation and harmonic filtering (RPC & HF) to reduce the reactive power and harmonic current down to the levels acceptable to the French/European 400 kV grid. This paper reports on the present design of the RPC & HF system taking account of the load power and grid requirements. The steady state and transient analysis has been performed using a detailed computer model which includes all main electrical parameters. The normal operating conditions and several different faults have been analysed and the main results are presented. The results show that the fault condition of fast load rejection may cause a relatively high overvoltage. Possible solutions to reduce the overvoltage are discussed.
机译:ITER线圈电源系统的特征在于非常大的AC / DC转换装置,其产生相对大量的无功和谐波电流。因此,ITER电源系统将包括大量无功功率补偿和谐波滤波(RPC&HF),以将无功功率和谐波电流降低到法式/欧洲400 kV栅格可接受的水平。本文报告了考虑到负载功率和网格要求的RPC和HF系统的本设计。使用具有包括所有主要电气参数的详细计算机模型进行了稳态和瞬态分析。已经分析了正常的操作条件和几种不同的故障,并提出了主要结果。结果表明,快速载荷抑制的故障条件可能导致相对高的过电压。讨论了减少过电压的可能解决方案。