The ITER Coil Power Supply System is characterised by a very large AC/DC conversion plant which produces a relatively high amount of reactive power and harmonic currents. Consequently, the ITER power supply system will include substantial reactive power compensation and harmonic filtering (RPC & HF) to reduce the reactive power and harmonic current down to the levels acceptable to the French/European 400 kV grid. This paper reports on the present design of the RPC & HF system taking account of the load power and grid requirements. The steady state and transient analysis has been performed using a detailed computer model which includes all main electrical parameters. The normal operating conditions and several different faults have been analysed and the main results are presented. The results show that the fault condition of fast load rejection may cause a relatively high overvoltage. Possible solutions to reduce the overvoltage are discussed.
机译:ITER线圈电源系统的特点是具有非常大的AC / DC转换设备,该设备会产生相对大量的无功功率和谐波电流。因此,ITER电源系统将包括大量的无功功率补偿和谐波滤波(RPC&HF),以将无功功率和谐波电流降低到法国/欧洲400 kV电网可接受的水平。本文报告了RPC和HF系统的当前设计,其中考虑了负载功率和电网要求。已使用包括所有主要电气参数的详细计算机模型执行了稳态和瞬态分析。分析了正常的工作条件和几种不同的故障,并给出了主要结果。结果表明,快速甩负荷的故障状态可能会导致较高的过电压。讨论了减少过电压的可能解决方案。