首页> 外文会议>European Conference on Power Electronics and Applications >STATCOM Operation under single line-ground system faults with magnetic saturation in series connected transformers based 48-pulse voltage-source converter
【24h】

STATCOM Operation under single line-ground system faults with magnetic saturation in series connected transformers based 48-pulse voltage-source converter

机译:STATCOM在单线接地系统下的故障,磁饱和在串联串联变压器中的48脉冲电压源转换器

获取原文

摘要

In this paper, we investigate an “emergency PWM” method to prevent over-currents in VSC based STATCOM and control transformer magnetic saturation under single line-ground (SLG) power system faults. The 100MVA 48-pulse VSC topology is based on four series connected transformers on the primary side and each transformer secondary is connected to a 3Ф, 3-level Neutral Point Connected (NPC) VSC, with a common dc bus. A practical issue of impact of slightly different saturation (B-H) characteristics of series connected transformers, on VSC performance is investigated for SLG faults in the power system. The detailed simulation results for a 48-pulse GTO thyristor based VSC ±100 MVA STATCOM connected to a 2-bus power system under SLG system faults validate that the proposed “emergency PWM” enables STATCOM operation under transformer saturation without over-currents in the GTO devices. The proposed “emergency PWM” strategy prevents STATCOM tripping under SLG power system faults.
机译:在本文中,我们调查了“紧急PWM”方法,以防止基于VSC的Statcom和控制变压器磁饱和度的过电流在单线 - 地面(SLG)电源系统故障下。 100MVA 48脉冲VSC拓扑基于初级侧的四个系列连接的变压器,每个变压器辅助连接到3Ф,3级中性点连接(NPC)VSC,具有公共直流总线。对电力系统中的SLG故障进行了研究,对VSC性能略有不同饱和度(B-H)特性的实际问题。 48脉冲GTO晶闸管基于VSC±100 MVA Statcom的详细仿真结果连接到SLG系统故障下的2柱电源系统验证了所提出的“紧急PWM”,在变压器饱和度下使Statcom运行能够在GTO中没有过度电流设备。提出的“紧急PWM”策略可防止SLG电源系统故障下的Statcom跳闸。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号