【24h】

A Locating Diagnosis of Partial Discharge on Cross-bonding Ground System

机译:跨粘接地面系统局部放电定位诊断

获取原文

摘要

At the present, Thailand has turned the attention to Underground Cable (UC) systems and trends to use it more to safety, stability and reliability of electrical system. However, one problem that can affect to this electrical system is the Partial Discharge (PD) problem. Most of PD problems are caused by incomplete installation, maintenance reason and insulation degradation on the weakest part, especially cable joint. This paper proposes a method of analysis to locate the PD source in UC systems with Cross Bonding (CB) focus on cable joints. This work has carried out in laboratory on CB system model using 50ohm R58 coaxial cable instead of underground cable. The PD detection technique according to IEEE 400.3 standard with a RFCT sensor to refer the appropriate signal. This work uses a PD diagnostic device that can filter noise from the PD groups and separate groups of PD for greater analysis accuracy. To determine which cable joint is PD source and to be able to fix it on the spot. The PD signal analysis are performed by using time of arrival method considered together with the characteristics and the polarity of the PD pulse.
机译:目前,泰国已将注意力推动到地下电缆(UC)系统和趋势,以便更适合电气系统的安全性,稳定性和可靠性。然而,可能影响该电气系统的一个问题是局部放电(PD)问题。大多数PD问题是由最弱部件的不完全安装,维护原因和绝缘劣化引起的,尤其是电缆接头引起的。本文提出了一种分析方法,以在具有交叉键合(CB)的UC系统中定位PD源的PD源对焦于电缆接头。这项工作在CB系统模型的实验室中进行了使用50OHM R58同轴电缆而不是地下电缆进行的。根据IEEE 400.3标准的PD检测技术,具有RFCT传感器来参考相应的信号。这项工作使用PD诊断设备,可以从PD组滤波噪声和单独的PD组,以获得更高的分析精度。确定哪个电缆接头是PD源,并能够在现场固定它。通过使用与PD脉冲的特性和极性一起考虑的到达时间来执行PD信号分析。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号