CHOICE OF THE FORM OF THE TEST SWITCHING PULSE AND AMENDMENTS ON ATMOSPHERIC CONDITIONS FOR UHV EXTERNAL INSULATION

机译:选择开关脉冲形式和对特高压外部绝缘材料的大气条件进行修正

获取原文

摘要

Experimental data of electric strength of insulation structures of UHVAC equipment (voltageabove 800 kV) are resulted at change of time to peak of positive polarity switching impulsefrom tens up to 5500 μs.It is shown, that at time to peak of aperiodical impulse τp in interval 400 μs – 800 μs externalinsulation of 1000 kV-1200 kV equipment possesses the minimal electric strength.In this range of time to peak of an impulse τp electric strength of concrete UHV insulationstructure depends a little on time to peak of an impulse.For test of external insulation of UHV electric equipment (1000 kV-1200 kV) it is offered toaccept as a standard switching impulse of aperiodical form with time to peak 500 μs and/or anunipolar oscillatory impulse with time to peak 1000 μs.Results of experimental researches on influence of atmospheric conditions on electric strengthof UHV external insulation at stress of unipolar oscillatory switching impulses of positivepolarity are also presented.Essential decrease in discharge voltage of external insulation in process of decrease ofnegative air temperature (T < 0 °C) is revealed. It is established, that correction factors onatmospheric conditions recommended by IEC Publication 60060-1 which are valid for area ofpositive air temperatures, cannot be widespread to area of negative air temperatures. Withreference to this area of atmospheric air temperatures correction factors on atmosphericconditions are offered for discussion.
机译:UHVAC设备绝缘结构的电气强度的实验数据(电压 800 kV以上)是在时间变化到正极性切换脉冲的峰值时产生的 从数十到5500μs。 结果表明,在非周期性脉冲τp达到峰值的时间间隔为400μs– 800μs,外部 1000 kV-1200 kV设备的绝缘具有最小的电气强度。 在此时间范围内,达到峰值τp的混凝土特高压绝缘的电气强度 结构在某种程度上取决于脉冲的峰值时间。 用于特高压电气设备(1000 kV-1200 kV)的外部绝缘测试 接受非周期性形式的标准开关脉冲,其峰值时间为500μs和/或 单极振荡脉冲,峰值时间为1000μs。 大气条件对电气强度影响的实验研究结果 高压外绝缘对正极性单极振荡开关脉冲应力的影响 极性也被提出。 减少绝缘过程中外部绝缘放电电压的本质下降 出现负空气温度(T <0°C)。已经确定,校正因子 IEC出版物60060-1推荐的适用于以下区域的大气条件 空气温度为正数时,不能扩展到空气温度为负数的区域。和 参考该区域的大气温度大气校正因子 提供了讨论条件。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号