首页> 外文会议>Conference on Thermal Power Plants >A proposed heterogeneous distribution of water for natural draft dry cooling tower to improve cooling efficiency under crosswind
【24h】

A proposed heterogeneous distribution of water for natural draft dry cooling tower to improve cooling efficiency under crosswind

机译:一种拟议的天然干燥冷却塔水的异构分布,提高交叉风下的冷却效率

获取原文

摘要

Crosswind can significantly affect the cooling performance of natural draft dry cooling towers. In this study, a heterogeneous distribution of water has been proposed to increase the cooling performance of the tower under crosswind. This idea is based on the fact that under wind condition, the mean values of convective heat transfer coefficients at the windward radiators are more than that of the leeward ones. Therefore, the windward radiators may be worthy to get higher percentages of the hot circulative water in comparison to the leeward faces. In the present research work, CFD method has been used to evaluate this proposal. It has been shown that the improvement compared to the usual uniform regime, under the proposed heterogeneous distribution of water is 1.67(%) at the investigated wind velocity.
机译:跨越式可以显着影响天然干燥冷却塔的冷却性能。 在这项研究中,已经提出了一种非均相分布的水分布,以增加跨华塔下塔的冷却性能。 该思想基于以下情况:在风条件下,迎风辐射器处的对流传热系数的平均值大于背风的平均值。 因此,与背风面相比,迎风散热器可能值得获得更高百分比的热环水。 在本研究工作中,CFD方法已被用于评估此提议。 已经表明,与通常的均匀制度相比的改进,在所提出的异构分布下,在调查的风速下是1.67()。