Crosswind can significantly affect the cooling performance of natural draft dry cooling towers. In this study, a heterogeneous distribution of water has been proposed to increase the cooling performance of the tower under crosswind. This idea is based on the fact that under wind condition, the mean values of convective heat transfer coefficients at the windward radiators are more than that of the leeward ones. Therefore, the windward radiators may be worthy to get higher percentages of the hot circulative water in comparison to the leeward faces. In the present research work, CFD method has been used to evaluate this proposal. It has been shown that the improvement compared to the usual uniform regime, under the proposed heterogeneous distribution of water is 1.67(%) at the investigated wind velocity.
机译:侧风会严重影响自然通风干式冷却塔的冷却性能。在这项研究中,已经提出了水的非均质分布,以提高侧风下塔的冷却性能。这个想法是基于这样的事实,即在有风的情况下,迎风散热器处的对流传热系数的平均值要大于背风散热器的对流传热系数的平均值。因此,与背风面相比,迎风散热器可能值得获得更高百分比的热循环水。在当前的研究工作中,CFD方法已用于评估该建议。结果表明,在研究的风速下,在建议的水的非均质分布下,与通常的均匀方案相比,该改进为1.67(%)。