首页> 外文会议>International Conference on Renewable Energy Research and Applications >Investigation over/under-voltage protection of passive islanding detection method of distributed generations in electrical distribution systems
【24h】

Investigation over/under-voltage protection of passive islanding detection method of distributed generations in electrical distribution systems

机译:电气配电系统中分布式代代被动岛检测方法的研究进展/欠压保护

获取原文

摘要

The objective of this paper is to investigate over/under-voltage protection (OVP/UVP) of passive islanding detection method of distributed generations in electrical distribution systems. The IEEE 14-bus system is simulated with Powerworld simulator. The studies show relationship between load and NDZ with DG in power system. The simulation results have showed that the change of load will affect the rate of transfer of ΔP uneven. If OVP/UVP of passive islanding detection method used algorithm with ΔP/P equation for decision, it may not be able to detect islanding condition In addition, if the multiple DGs in electrical distribution systems can replace active power of utility system, the OVP/UVP of passive islanding detection method cannot detected the state of islanding.
机译:本文的目的是研究电气分配系统中分布代的被动岛检测方法的过电压/欠压保护(OVP / UVP)。 使用PowerWorld Simulator模拟IEEE 14总线系统。 研究表明了电力系统中DG的负载与NDZ之间的关系。 仿真结果表明,负载的变化会影响&#x0394的转移速率; p不均。 如果无源孤岛检测方法的OVP / UVP使用算法与Δ p / p方程进行决定,它可能无法检测孤岛条件,如果电气分配系统中的多个DG可以替代公用事业系统的有功功率 ,无源孤岛检测方法的OVP / UVP无法检测到岛屿的状态。