Partial Discharge (PD) measurement is an effective method to detect degradation processes in medium and high voltage equipment. As an example, after-laying PD test have become mandatory in many countries as a commissioning test for high voltage cable systems. This type of test can assess the presence of defects just after installation, but thermal cycling, electrical and thermal stress as well as contamination can lead to the onset of defects at a later time. To cope with defects arising during operation, the key is PD monitoring (offline tests are often too costly in terms of equipment, personnel and loss of revenues). This paper presents the application a of permanent PD monitoring system based on a Ultra-Wide band (UWB) detector to high voltage transition joints linking old fluid-filled cables with new XLPE cable lines. These cable accessories are highly critical because of the complexity of their insulation system and the fact they are realized on field (uncontrolled environment). The innovative monitoring scheme fully exploits the benefits coming from using a UWB detector, i.e., selective tracking of PD based on PD pulse characteristics. This approach enables to trend various PD sources separately, highlighting those that are associated with degradation phenomena within the insulation system. This approach will be unraveled and demonstrated by monitoring data coming from two cable lines.
机译:局部放电(PD)测量是检测中高压设备中降解过程的有效方法。例如,作为许多高压电缆系统的调试测试,在许多国家/地区都必须进行后置PD测试。这种类型的测试可以在安装后立即评估缺陷的存在,但是热循环,电和热应力以及污染会导致缺陷在稍后的时间出现。为了应对操作过程中出现的缺陷,关键是PD监视(离线测试在设备,人员和收入损失方面通常过于昂贵)。本文介绍了基于超宽带(UWB)检测器的永久性PD监测系统在高压过渡接头上的应用,该过渡接头将旧的充液电缆与新的XLPE电缆线路连接起来。这些电缆附件非常重要,因为它们的绝缘系统很复杂,而且实际上是在现场(不受控制的环境)实现的。创新的监视方案充分利用了使用UWB检测器带来的好处,即基于PD脉冲特性选择性跟踪PD。这种方法可以使各种PD源分别趋向,从而突出显示与绝缘系统内的退化现象相关的那些源。将通过监视来自两条电缆线的数据来阐明和演示这种方法。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号