首页> 外文期刊>Elektrie >On-Line Condition Monitoring of High Voltage Equipment in Substations: Partial Discharges and Pollution Leakage Current
【24h】

On-Line Condition Monitoring of High Voltage Equipment in Substations: Partial Discharges and Pollution Leakage Current

机译:变电站高压设备的在线状态监测:部分放电和污染泄漏电流

获取原文
获取原文并翻译 | 示例
           

摘要

This paper reports laboratory development and field trials of two on-line condition-monitoring systems for high voltage power equipment. The first system is for on-line measurement of partial discharges and for the evaluation of their parameters. The principle used utilises capturing partial discharges by means of a current transducer (Rogowski coil), fibre-optic transmission link and fast computerised wide-band data acquisition system. The second condition monitoring system is for continuous on-line measurement and recording of the surface leakage current on polluted insulators of high voltage equipment. A signal proportional to the leakage current is fed into a sensor the output of which is transmitted via a fibre-optic link to the data acquisition system. This system enables continuous recording of the RMS value of the leakage current. Both partial discharges and pollution monitoring systems were tested for six months in a high voltage substation where the computerised data acquisition equipment was placed in the control room. These relatively low-cost systems proved to be reliable, robust and safe to use under the harsh environmental and electromagnetic conditions in HV substations.
机译:本文报告了高压电力设备两个在线状态监测系统的实验室开发和现场试验。第一系统用于部分放电的在线测量和对其参数的评估。使用的原理利用当前换能器(Rogowski线圈),光纤传输链路和快速计算机化宽带数据采集系统捕获部分放电。第二种状态监测系统用于在高压设备污染绝缘体上连续在线测量和记录表面漏电流。与漏电流成比例的信号被馈送到传感器中,其输出通过光纤链路发送到数据采集系统。该系统可以连续记录漏电流的RMS值。在高压变电站中测试了部分放电和污染监测系统,将计算机化数据采集设备放置在控制室中。这些相对低成本的系统证明在HV变电站的恶劣环境和电磁条件下可靠,稳健和安全。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号