SUMMER OF 1998 LOWER RIO GRANDE VALLEY OPERATIONS

机译:1998年夏里奥格兰德河谷行动

获取原文
获取外文期刊封面目录资料

摘要

At 2:57 PM on July 3,1998, CPUs Rio Hondo substation received some light misty rainfall. Two separate sets of free-standing 345KV current transformers (CTs) flashed-over resulting in two CΦ?line-to-ground faults. There were approximately 29 seconds between the two CΦ?line-to-ground faults. This disturbance resulted in the opening of three 345KV transmission lines, two 345/138KV autotransformers, two generating units, and the loss of at least 352 MW of load across CPUs system in the Lower Rio Grande Valley. The intention of this paper is to share an understanding of the operations at the Rio Hondo 345kV Station and its impact on the Lower Rio Grande Valley Power System.
机译:1998年7月3日下午2:57,CPU Rio Hondo变电站收到了一些薄雾。两组独立的独立式345KV电流互感器(CT)闪动,导致两个CΦ?线对地故障。两次CΦ?线对地故障之间大约相隔29秒。这种干扰导致打开了三个345KV输电线路,两个345 / 138KV自耦变压器,两个发电机组,并降低了下里奥格兰德河谷CPU系统的负载至少352 MW。本文的目的是就里奥本多345kV站的运行及其对下里奥格兰德河谷电力系统的影响达成共识。