摘要

Simulations and high voltage field tests indicate that unacceptable and unexpected motor terminal overvoltages and waveform shapes can occur in the normal operating range with multilevel drive systems. These waveforms (if unattended) would have resulted in premature motor insulation failures. A case study of an 11 kV multilevel system is discussed. Simulations and calculations confirm the theory of resonance overvoltages. Different solution possibilities are analyzed. Further simulations and investigations are performed to determine the optimal carrier frequency. Test results confirm that the proposed modification has the desired effect; with waveforms well within limits stipulated by international standards. Simplified equations and recommendations are provided to determine suitable application solutions.
机译:仿真和高压现场测试表明,在多级驱动系统的正常工作范围内,会出现不可接受的和意外的电机端子过电压和波形形状。这些波形(如果无人看管)会导致电动机过早绝缘故障。讨论了一个11 kV多电平系统的案例研究。仿真和计算证实了谐振过电压的理论。分析了不同的解决方案可能性。进行进一步的仿真和研究以确定最佳载波频率。测试结果证实了所提出的修改具有预期的效果;波形完全在国际标准规定的范围内。提供简化的公式和建议来确定合适的应用解决方案。