首页> 外文会议> >Development of the high accuracy Impedance Type Fault Locator using a Mode Transformation
【24h】

Development of the high accuracy Impedance Type Fault Locator using a Mode Transformation

机译:利用模式转换开发高精度阻抗型故障定位仪

获取原文

摘要

The authors have developed an innovative FL (Fault Locator) System, which takes the 3-phase unbalance into consideration by simulation of a power transmission line with the distributed constant circuit and use of the theory of mode transformation. The system developed by the authors automatically reads the waveform data of voltage and current from the fault recorder which is time-synchronized to the GPS (Global Positioning System) and measures distance to the fault point using the above-mentioned data and power transmission system data which are set in advance. The authors carried out field tests of the FL System developed by the authors on fourteen lines of the 66kV power transmission system of TEPCO (Tokyo Electric Power Company) and obtained good results that showed a mean error of 0.43 [km]. This paper presents these results.
机译:作者开发了一种创新的FL(故障定位器)系统,该系统通过使用分布式恒定电路模拟输电线路并使用模式转换理论来考虑三相不平衡。作者开发的系统自动从故障记录仪读取电压和电流的波形数据,并与GPS(全球定位系统)进行时间同步,并使用上述数据和电力传输系统数据测量到故障点的距离预先设置的。作者在东京电力公司66 kV输电系统的14条线路上对作者开发的FL系统进行了现场测试,并获得了良好的结果,平均误差为0.43 [km]。本文介绍了这些结果。