首页> 外文会议> >Reduction of stress voltages at control equipment terminals in a substation through inductive coupling between cable core and sheath
【24h】

Reduction of stress voltages at control equipment terminals in a substation through inductive coupling between cable core and sheath

机译:通过电缆芯与护套之间的电感耦合降低变电站控制设备端子处的应力电压

获取原文

摘要

Considerable potential differences can develop between different parts, of an electric station's grounding grid during fault conditions, when circulating currents of great magnitude are involved. As a result, communications or control wires extending between these locations can subject the equipment they serve to damaging stress voltages. A limited reduction of the stress voltages can be achieved by increasing the density of grounding grid conductors. This paper examines a highly effective method of reducing stress voltages by enclosing these wires in low impedance metallic sheaths or conduit, and bonding the latter outer conductors to the grounding grid at the wire extremities.
机译:当涉及大电流时,在故障情况下,电站接地网的不同部分之间可能会产生相当大的电位差。结果,在这些位置之间延伸的通信或控制线可能会使它们所服务的设备遭受损坏的电压。可以通过增加接地栅极导体的密度来实现应力电压的有限降低。本文研究了一种有效的降低应力电压的方法,该方法是将这些导线封装在低阻抗的金属护套或导线管中,然后将后者的外部导体与导线末端的接地网格相连。