When distribution power lines run normally, there is asymmetrical current and voltage component including negative sequence and zero sequence components. So non-communication protection based on sequence components might mal-operate or mis-operate in the cases. The paper proposed a new noncommunication protection scheme based on fault component for distribution line. The protection can be applied to different neutral grounding mode including direct and indirect grounding neutral system and isn't affected by normal running asymmetrical component. According to the fault component (or the incremental quantities of three sequence component), it can assure that one end breaker of fault line trips as quickly as possible and other end breaker is accelerated to trip. Simulation shows that the protection scheme is both correct and effective.
机译:当配电电源线正常运行时,存在不对称的电流和电压分量,包括负序分量和零序分量。因此,在这种情况下,基于序列组件的非通信保护可能会误操作或误操作。提出了一种基于故障分量的配电线路非通信保护新方案。该保护可以应用于不同的中性点接地模式,包括直接和间接接地中性点系统,并且不受正常运行的不对称组件的影响。根据故障分量(或三序分量的增量),可以确保故障线路的一个末端断路器跳闸最快,而另一个末端断路器加速跳闸。仿真表明,该保护方案是正确有效的。