首页> 外文会议>International Conference on Power System Technology >Research on non-communication protection of distribution lines base don fault components
【24h】

Research on non-communication protection of distribution lines base don fault components

机译:基于故障组件的配电线路非通信保护研究

获取原文
获取外文期刊封面目录资料

摘要

When distribution power lines run normally, there is asymmetrical current and voltage component including negative sequence and zero sequence components. So non-communication protection based on sequence components might mal-operate or mis-operate in the cases. The paper proposed a new non-communication protection scheme based on fault component for distribution line. The protection can be applied to different neutral grounding mode including direct and indirect grounding neutral system and isn't affected by normal running asymmetrical component. According to the fault component (or the incremental quantities of three sequence component), it can assure that one end breaker of fault line trips as possible as quickly and other end breaker is accelerated to trip. A lot of simulation shows that the protection scheme is correct and effective.
机译:当分配电源线正常运行时,存在不对称电流和电压分量,包括负序列和零序列组件。因此,基于序列组件的非通信保护可能在案例中使用或错误运行。本文提出了一种基于分销线故障组件的新型非通信保护方案。保护可以应用于不同的中性接地模式,包括直接和间接接地中性系统,不受正常运行不对称组分的影响。根据故障组件(或三个序列分量的增量量),可以确保尽可能快速地和其他端断路器尽可能快地进行故障线路的一个结束断路器。许多仿真表明保护方案是正确且有效的。