A converter transformer with series-connected line-side windings for a DC link using voltage source converters

机译:具有串联连接的线侧绕组的转换器变压器,用于使用电压源转换器的直流母线

获取原文

摘要

A project is under way in Japan to develop a high-power voltage source converter system for future DC interconnection between AC networks and HVDC transmission. A 300 MW/AC 275 kV converter transformer with series-connected line-side windings for combination of multiple voltage source PWM converters in series on the AC side is being developed. Down-scaled transformer models were manufactured, and subjected to factory testing to verify the solutions for equalization of voltage sharing between the windings, prevention of DC magnetization in the core caused by the converter output voltages, and estimation of core losses when the core is magnetized by a PWM converter. Based on the design criteria confirmed by factory testing, 53 MVA GTO-based converters and converter transformers were installed for a prototype back-to-back link between actual 50 Hz/66 kV and 60 Hz/275 kV systems, and field testing is being conducted. The behavior of magnetic flux across the core during operation was monitored by embedded Hall-effect sensors. Satisfactory results were obtained.
机译:日本正在进行一项开发大功率电压源转换器系统的项目,该系统用于将来交流网络和高压直流输电之间的直流互连。正在开发一种300 MW / AC 275 kV转换器变压器,该转换器变压器具有串联的线侧绕组,用于在AC侧串联多个电压源PWM转换器。制造了缩小比例的变压器模型,并经过工厂测试,以验证以下解决方案:绕组之间的电压均分均衡,防止由转换器输出电压引起的铁心中的DC磁化以及估算铁心被磁化时的铁心损耗通过PWM转换器。根据工厂测试确定的设计标准,为实际50 Hz / 66 kV和60 Hz / 275 kV系统之间的背靠背原型连接安装了53个MVA GTO型转换器和转换器变压器,并且正在进行现场测试。实施。嵌入式霍尔效应传感器可监控运行过程中磁芯上的磁通量行为。获得满意的结果。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号