The concentration of the chemical furfural in transformer oil is well known to be an indicator of the extent to which the paper insulation of the windings has deteriorated. However, the majority of publications on this topic are based on small-scale laboratory investigations with very little on field experience with power transformers. This paper reports the analysis of data on the concentration of furfural in oil samples from 310 transmission transformers. The data indicated that there was no discernible steady increase in the furfural concentration (FC) but that occasionally a large increment in FC occurred which was assumed to be due to significant overloads. This was demonstrated by: repeat measurements separated by up to 2 years; by a tendency for high-FC transformers to be over 12 years old and located in districts known to have had a high probability of overload in the 1980s; and by a simulation based on this model which showed a similar pattern of occasional high FCs but most transformers lasting 20 years or more without significant deterioration. The beneficial effect of changing the oil on high-FC transformers to limit further deterioration is also discussed.
机译:众所周知,变压器油中化学糠醛的浓度是绕组的纸绝缘性能下降程度的指标。但是,有关此主题的大多数出版物都是基于小型实验室研究,很少有电力变压器的现场经验。本文报告了有关310台输电变压器油样中糠醛浓度的数据分析。数据表明糠醛浓度(FC)没有明显的稳定增加,但偶尔会发生FC的大幅增加,这可能是由于明显的超负荷所致。这可以通过以下方式得到证明:重复测量,最长间隔2年;高FC变压器已经使用了12年以上,并且位于1980年代已知有超载可能性的地区,这是一种趋势;并基于此模型进行的仿真表明,偶尔出现的高FC表现出相似的模式,但大多数变压器可使用20年或更长时间,而不会出现明显的劣化。还讨论了在高FC变压器上更换机油以限制进一步恶化的有益效果。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号