首页> 外文会议> >Retrofitting obsolete 15 kV switchgear for a pulp and paper mill
【24h】

Retrofitting obsolete 15 kV switchgear for a pulp and paper mill

机译:为制浆造纸厂改造过时的15 kV开关柜

获取原文

摘要

A case study involving the resolution of certain engineering and logistical problems encountered in upgrading existing obsolete 15 kV 750 MVA air magnetic switchgear to meet a 1000 MVA application at an integrated pulp and paper mill is presented. The existing 15 kV switchgear is essential to the mill's operation, and could not be shut down for construction purposes. The solution was to utilize a retrofitting technique. The technique involves removing the existing circuit breaker element from its cubicle and stripping off everything associated with the old breaker. The stripped breaker element frame is refitted with state-of-the-art vacuum interrupters. The retrofitted assembly is reinserted into the existing cubicle and placed into service. The mill site application requirements, the selection of a qualified retrofitter, the retrofitting procedure, the benefits of retrofitting and the testing and installation experience are described.
机译:案例研究涉及解决某些工程和后勤问题的问题,这些问题是在集成的制浆造纸厂升级现有的过时的15 kV 750 MVA空气电磁开关设备以满足1000 MVA的应用时遇到的。现有的15 kV开关设备对于工厂的运行至关重要,并且无法出于建设目的而关闭。解决的办法是利用改造技术。该技术包括将现有断路器元件从其柜体中取出,并剥离与旧断路器相关的所有东西。剥开的断路器元件框架重新安装了最先进的真空灭弧室。改装后的组件重新插入到现有的隔间中并投入使用。描述了工厂现场的应用要求,合格的加装工的选择,加装程序,加装的好处以及测试和安装经验。