Field-measurement of CO2 Level in General Hospital Wards in Nanjing

机译:南京市综合医院病房二氧化碳水平的现场测量

获取原文

摘要

Hospital indoor air quality (IAQ) has a significant impact on patients' and health care workers' health and the indoor carbon dioxide (CO2) level is considered to be an indicator to evaluate IAQ in some cases.This article presents a long-term field-measurement of indoor CO2 level in a general hospital ward in Nanjing.Four months' data are collected and analyzed to reveal variation rule of CO2 levels in wards in this periods.The results indicate that the variation rule of indoor CO2 level is associated to patients' living habit.The use of natural ventilation is capable to keep the indoor CO2 level below 1000 ppm in transition season while it is much higher in heating season due to closing openings to maintain thermal comfort.The results also demonstrate a “ω” shape of changing of CO2 levels within a day in heating season.
机译:医院的室内空气质量(IAQ)对患者和医护人员的健康有重大影响,在某些情况下,室内二氧化碳(CO2)水平被认为是评估IAQ的指标。本文提出了一个长期的领域南京某综合病房室内CO2水平的测定。收集并分析了四个月的数据,揭示了该期间病房中CO2水平的变化规律。结果表明,室内CO2水平的变化规律与患者相关。生活习惯。使用自然通风能够使过渡季节的室内CO2含量保持在1000 ppm以下,而由于关闭开口以保持热舒适性,采暖季节的室内CO2含量要高得多。结果还显示出“ω”形采暖季节一天之内二氧化碳水平的变化。