首页> 外文会议>Intelligent System Design and Engineering Application (ISDEA), 2012 Second International Conference on >Withstand Capability Testing and Limitation Measurements on Du/dt and Di/dt of Thyristor Valve of the Controllable Metal Oxide Surge Arrester
【24h】

Withstand Capability Testing and Limitation Measurements on Du/dt and Di/dt of Thyristor Valve of the Controllable Metal Oxide Surge Arrester

机译:可控金属氧化物避雷器晶闸管阀的Du / dt和Di / dt承受能力测试和极限测量

获取原文

摘要

Du/dt is voltage rise rate in off-state of thyristor. Di/dt is current rise rate in on-state of thyristor. Du/dt and di/dt are key parameters that determine working security of thyristor valve of the controllable metal oxide surge arrester (CMOA, shortly). Combining with the Jindongnan via Nan yang to Jingmen UHV AC pilot project of China, the maximal values of du/dt and di/dt of thyristor were simulated. Required parameters were put forward. The maximal du/dt was 28.3kV/μs and the maximal di/dt was 87kA/μs. Du/dt and di/dt mustn''t exceed critical value du/dtcrit and di/dtcrit. Though du/dtcrit and di/dtcrit could be provided by factory, they should be tested by actual application condition because actual application condition may be different from the testing condition. So, by testing, the maximal withstand capacity of du/dt and di/dt was tested by actual application condition. Comparing test results with required parameters indicated that the maximal withstand capacity of du/dt of 2.0 to 3.0 inch thyristor was not less than 45kV/μs which was more than required 28.3kV/μs. Limiting measurement was not needed. The maximal withstand capacity of di/dt was between 865 A/μs and 910A/μs which was much less than the required 87kA/μs. Limiting measures were needed. Study indicated that di/dt could be limited within allowable range by current limited reactor. However reactor may affect limiting switching over voltage of CMOA. So, appropriate values of reactor should be selected. Study indicated that reactor value might be between 3 and 5 mH. In such range, the current limited reactor has wee influence on CMOA limiting effect on switching over voltage.
机译:Du / dt是晶闸管关断状态下的电压上升率。 Di / dt是晶闸管导通状态下的电流上升速率。 Du / dt和di / dt是决定可控金属氧化物避雷器(CMOA,简称CMOA)晶闸管阀工作安全性的关键参数。结合南阳至晋东南至荆门特高压交流试验项目,对可控硅的du / dt和di / dt最大值进行了模拟。提出了必要的参数。最大du / dt为28.3kV /μs,最大di / dt为87kA /μs。 Du / dt和di / dt不得超过临界值du / dt crit 和di / dt crit 。尽管du / dtcrit和di / dt crit 可以由工厂提供,但应根据实际应用条件进行测试,因为实际应用条件可能与测试条件不同。因此,通过测试,通过实际应用条件测试了du / dt和di / dt的最大承受能力。将测试结果与所需参数进行比较表明,2.0 / 3.0英寸晶闸管的du / dt的最大承受能力不小于45kV /μs,大于所需的28.3kV /μs。不需要极限测量。 di / dt的最大承受能力在865 A /μs至910A /μs之间,远低于所需的87kA /μs。需要采取限制措施。研究表明,di / dt可通过限流反应器限制在允许范围内。但是,电抗器可能会限制CMOA的切换电压。因此,应选择合适的电抗器值。研究表明,反应堆值可能在3-5 mH之间。在此范围内,限流电抗器对CMOA限制切换电压的影响微不足道。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号