首页> 外文会议>Intelligent System Design and Engineering Application (ISDEA), 2012 Second International Conference on >The Characteristic of Transformer Winding Inter-turn Discharge under Sulphur Corrosion and Thermal Ageing
【24h】

The Characteristic of Transformer Winding Inter-turn Discharge under Sulphur Corrosion and Thermal Ageing

机译:硫腐蚀和热老化下的变压器绕组匝间放电特性

获取原文

摘要

In order to study transformer winding inter-turn discharge caused by corrosive sulphur, A series of comparative tests were designed. Firstly, a series of accelerated ageing tests of transformer oil were completed. All the oil samples were processed by dehydration and degasification, then divided into three groups, one group samples were added with insulation paper wrapped-copper electrodes and sulphur. while the other group samples were added with electrodes but no sulphur, then aged under 130°C for 14, 24 and 30 days respectively. Next a number of experiments were taken to research the discharge process according to IEC standard methods. The results indicated that the partial discharge inception voltage by corrosive sulfide dropped very significantly compared with the electrodes without sulphur, and it reduced with the ageing time, but the breakdown voltage variation was much smaller and during the whole developing process, the discharge continuing time increased from 14 days to 24 days, then decreased for 24 days to 30 days. At the same time, the insulation papers are taken to measure the tear resistance, which shows the same trend with the discharge continuing time, Those results are valuable for evaluating the transformer condition order of severity corroded by corrosive sulphur and helpful to evaluating the large transformer life and monitoring the condition of large electrical power transformers.
机译:为了研究腐蚀性硫引起的变压器绕组匝间放电,设计了一系列比较试验。首先,完成了一系列变压器油的加速老化试验。所有的油样品都经过脱水和脱气处理,然后分为三组,一组样品中添加了绝缘纸包裹的铜电极和硫。而其他组的样品中则添加了电极但没有硫,然后分别在130°C下老化了14天,24天和30天。接下来,根据IEC标准方法进行了许多实验,以研究放电过程。结果表明,与不使用硫磺的电极相比,腐蚀性硫化物引起的局部放电起始电压下降得非常明显,并且随着老化时间的延长而降低,但击穿电压的变化却很小,并且在整个显影过程中,放电持续时间增加了。从14天减少到24天,然后减少24天减少到30天。同时,用绝缘纸测量了抗撕裂强度,与放电持续时间呈相同趋势。这些结果对于评估变压器条件受硫磺腐蚀的严重程度有重要价值,有助于评估大型变压器。大型电力变压器的使用寿命并监视其状态。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号