【24h】

Mov surge arrester's failure analysis

机译:Mov避雷器的故障分析

获取原文

摘要

This paper provides catastrophic failure analysis of all three (3) station-class metal-oxide varistor (MOV) surge arresters located inside the metal-clad switchgear. All three surge arresters failed causing major damage to the switchgear without any evidence of switching surge activity. Analysis concludes that the B-phase surge arrester internal damage led to its thermal runaway. The exact cause of this arrester internal damage remains unknown. The passage of a ground fault current through the arrester damaged the mounting plate and the subsequent heat transfer caused the phase-phase-ground short circuit through the other arresters. All arresters and the switchgear enclosure were damaged. Investigation into the cause of these events is the subject of this paper. Evaluation of the existing power system configuration and arresters' installation inside the switchgear cubicle are included in the failure analysis. To minimize such failures, installation recommendations for the surge arresters inside the medium-voltage switchgear are also included in the paper.
机译:本文提供了位于金属外壳开关柜内的所有三(3)个站级金属氧化物变阻器(MOV)电涌放电器的灾难性故障分析。所有三个电涌放电器均未发生故障,从而对开关柜造成了严重损坏,而没有任何有关切换电涌活动的迹象。分析得出的结论是,B相电涌放电器的内部损坏导致其热失控。避雷器内部损坏的确切原因尚不清楚。接地故障电流通过避雷器会损坏安装板,随后的传热导致相接地短路通过其他避雷器。所有避雷器和开关柜外壳均损坏。对这些事件的原因进行调查是本文的主题。故障分析包括对现有电力系统配置的评估以及开关柜内避雷器的安装。为了最大程度地减少此类故障,本文还包括中压开关柜内的电涌放电器的安装建议。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信