首页> 外文OA文献 >Studies of in-service and laboratory failures of metal-oxide distribution surge arresters
【2h】

Studies of in-service and laboratory failures of metal-oxide distribution surge arresters

机译:金属氧化物分布电涌放电器在役和实验室故障的研究

摘要

We describe the findings from tests and inspections of arresters withdrawn from service, the results of laboratory studies with multipulse lightning currents and high temporary over-voltages, and comparisons of in-service and laboratory failure modes. We show that gapped metal-oxide arresters are vulnerable to degradation from moisture ingress in the field and that the main causes of gapless arrester failures in the field and in the laboratory include very high temporary over-voltages and lightning strikes with multiple strokes.
机译:我们描述了退役避雷器的测试和检查结果,多脉冲雷电流和高临时过电压的实验室研究结果以及在役和实验室故障模式的比较。我们表明,有间隙的金属氧化物避雷器很容易因田间水分进入而退化,并且现场和实验室无间隙避雷器故障的主要原因包括非常高的临时过电压和多次冲击的雷击。