Numerical simulations of a clean room were conducted by software FDS5.3 using large-eddy simulation (LES). A computational fluid dynamics (CFD) model was first verified by comparing computational results with results of reduced scale clean room fire tests. The temperature near the ceiling round the fire location with three sizes acetone liquid fire were then studied for a typical full-scale clean room. Results show that the temperature near the ceiling is varied mainly due to the heat release rate (HRR). When the fire area is 0.5 m (meter) × 0.5 m, the excess temperature, near the ceiling in a horizontal distance 4.5 m from the fire centre, is below 50 K (kelvin) during the whole process; when the fire area is 2.0 m × 0.5 m, the temperatures above the ambient (300K), near the ceiling in a horizontal distance respectively 0.5 m and 2.5 m from the fire centre, get 50 K almost at the same time. However, under air ventilation, the temperature next to ceiling decreases fast with distance from the fire, so the radius of the smoke spread along the ceiling becomes small.
机译:使用软件FDS5.3使用大涡模拟(LES)对洁净室进行了数值模拟。首先通过将计算结果与规模缩小的洁净室火灾测试的结果进行比较,来验证计算流体动力学(CFD)模型。然后,针对典型的全尺寸洁净室,研究了三种尺寸的丙酮液体火在着火位置附近天花板附近的温度。结果表明,天花板附近的温度变化主要是由于放热率(HRR)所致。当着火面积为0.5 m(米)×0.5 m时,在整个过程中,距离天花板着火中心4.5 m处的天花板附近的多余温度低于50 K(开尔文);当着火面积为2.0 m×0.5 m时,在距离火场0.5 m和2.5 m的水平距离天花板附近的环境温度(300K)以上,几乎同时获得50K。但是,在空气流通的情况下,天花板附近的温度随着距离火源的距离而迅速降低,因此沿着天花板传播的烟雾的半径变小。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号