首页> 外文会议>Electrical and Electronics Engineering, 2009. ELECO 2009 >The study of maximum loading point in investigation of capacitor performance with power electronic shunt devices
【24h】

The study of maximum loading point in investigation of capacitor performance with power electronic shunt devices

机译:电力电子分流器在电容器性能研究中的最大负载点研究

获取原文

摘要

One of the major causes of voltage instability is the reactive power limit of the system. Improving the system's reactive power handling capacity via Flexible AC transmission System (FACTS) devices is a remedy for prevention of voltage instability and hence voltage collapse. In this paper, the effects of Shunt Capacitor, SVC and STATCOM in Static Voltage Stability Margin Enhancement will be studied. The continuation power flow methods are proposed in case of the increasing loading of contingency. The IEEE-14 bus system is simulated to test the increasing loadability. It is found that these devices significantly increase the loadability margin of power systems.
机译:电压不稳定的主要原因之一是系统的无功功率限制。通过柔性交流输电系统(FACTS)设备提高系统的无功功率处理能力是防止电压不稳定并因此防止电压崩溃的一种补救措施。本文将研究并联电容器,SVC和STATCOM在提高静态电压稳定性裕度方面的作用。在突发事件负荷增加的情况下,提出了连续潮流方法。模拟IEEE-14总线系统以测试不断增加的负载能力。发现这些设备显着增加了电力系统的负载能力裕度。