首页> 外文会议>Control of Inter-Urban Road Networks >Limiting electric strength of vacuum electrode systems including combined breakdown
【24h】

Limiting electric strength of vacuum electrode systems including combined breakdown

机译:限制真空电极系统的电气强度,包括组合击穿

获取原文
获取原文并翻译 | 示例

摘要

There exists three types of emission sites, eventually being a place of initiation of electric breakdown in vacuum switching devices with a screened insulator. Using electrostatic field calculations, potential breakdown paths, which start at the emission site in a vacuum interrupter, have been analyzed. Combined breakdown includes a breakdown path across two vacuum gaps and formation of flashover along an insulator. The paper discusses physical models of electron current multiplication at the insulator surface leading to the breakdown initiation.
机译:存在三种类型的发射点,最终是带有屏蔽绝缘子的真空开关设备中引起电击穿的地方。使用静电场计算,分析了从真空灭弧室的发射位置开始的潜在击穿路径。组合击穿包括跨越两个真空间隙的击穿路径以及沿绝缘子的闪络形成。本文讨论了导致击穿开始的绝缘子表面电子电流倍增的物理模型。