【24h】

Performance Evaluation of Oil-free Chillers for Building Energy Performance Improvement

机译:无油制冷机的建筑节能性能评估

获取原文
获取原文并翻译 | 示例

摘要

This paper investigates how to improve the energy performance of central air-conditioning systems by using oil-free chillers.Three conventional water-cooled centrifugal chillers of equal capacity were replaced by three oil-free chillers of the same capacity in an existing system.Operating data for performance evaluation were logged at 1-hr intervals for over one year before and after the replacement.The superior coefficient of performance (COP) of oil-free chillers with variable speed control brought an energy saving of 9.6% in the total electricity consumption of a shopping arcade when they operated for a wide range of system cooling demands.Results of data envelopment analysis gave an average technical efficiency of 0.6 which ascertains an opportunity for performance enhancement.The system COP can be further improved by tightening the control in the temperature of supply chilled water and implementing even load sharing among chillers to meet the overall system capacity.
机译:本文研究了如何通过使用无油制冷机来改善中央空调系统的能源性能。在现有系统中,三台相同容量的常规水冷离心式制冷机被三台相同容量的无油制冷机所替代。更换前后每隔1小时记录一次用于性能评估的数据。具有变速控制的无油制冷机的卓越性能系数(COP)节省了9.6%的总电力消耗数据包络分析的结果显示平均技术效率为0.6,这确定了性能提升的机会。通过加强温度控制可以进一步改善系统COP供应冷水,并在冷水机之间实现均匀的负载分担,以满足系统的整体容量。