【24h】

Measurement and Analysis of the Groundwater Source Heat Pump System in Shenyang

机译:沉阳市地下水源热泵系统的测量与分析

获取原文

摘要

The test mainly consists of three parts, including the basic test parameters, the unit system test parameters and heat pump system test parameters. Based on the test data, the conclusion of indoor and outdoor temperature of this residential area, the temperature distribution of the heat pump system and the heating system can be drawn. The performance and operation cost of this system also can be calculated based on the test data. The changes of temperature parameters runs stable, which conducive to the long-term operation of the system. The performance coefficient of the heat pump unit was about 2.33, and the energy efficiency of the heat pump system can reach 2.65. Ground source heat pump for heating and cooling operation cost was 28.3 yuan/m~2 throughout the year, saving about 21.39% when compared with the municipal heat supply network and central air conditioning system.
机译:该测试主要由三个部分组成,包括基本测试参数,单元系统测试参数和热泵系统测试参数。根据测试数据,可以得出该居住区的室内和室外温度的结论,热泵系统和供暖系统的温度分布。该系统的性能和运行成本也可以根据测试数据进行计算。温度参数的变化运行稳定,有利于系统的长期运行。热泵机组的性能系数约为2.33,热泵系统的能效可达到2.65。全年地暖供热运行费用地源热泵为28.3元/ m〜2,比市政供热管网和中央空调系统节省约21.39%。