Voltage stability analysis of a wind hub using Thévenin equivalent models estimated from measured data

机译:使用测得的数据估算的Thévenin等效模型对风轮毂进行电压稳定性分析

获取原文
获取原文并翻译 | 示例

摘要

This paper provides a method to estimate Thévenin equivalent models for voltage stability analysis of a wind hub with about 600 MW of rated generation. The estimation uses 24-hour SCADA data on two medium voltage transmission lines. The estimation is based on a recently developed method whose objective is to find, from long data records, a fixed Thévenin reactance value that yields a mostly fixed Thévenin voltage. This method is reliable as it does not perform curve fitting through data points that may be noisy and exhibit little variations. The load bus voltage calculated from the estimated Thévenin parameters matches well with the measured load bus voltage.
机译:本文提供了一种方法,用于估算约600兆瓦额定发电量的风轮毂的电压稳定性分析的维南等效模型。估算使用两条中压传输线上的24小时SCADA数据。该估计基于最近开发的方法,其目的是从长数据记录中找到固定的Thevenin电抗值,该值会产生一个大致固定的Thevenin电压。该方法是可靠的,因为它不会对可能有噪声且几乎没有变化的数据点执行曲线拟合。根据估算的Thevenin参数计算得出的负载母线电压与测得的负载母线电压非常匹配。