首页> 外文期刊>Power Delivery, IEEE Transactions on >An Equivalent Single-Infeed Model of Multi-Infeed HVDC Systems for Voltage and Power Stability Analysis
【24h】

An Equivalent Single-Infeed Model of Multi-Infeed HVDC Systems for Voltage and Power Stability Analysis

机译:用于电压和功率稳定性分析的多馈HVDC系统的等效单馈模型

获取原文
获取原文并翻译 | 示例
           

摘要

In this paper, an equivalent single-infeed model of a multi-infeed HVDC system is derived to lend theoretical basis for defining an index called equivalent effective short-circuit ratio (EESCR), which can resolve the ambiguity when applying the effective short-circuit ratio (ESCR) concept for the single-infeed to multi-infeed HVDC systems. Moreover, a Critical EESCR is derived analytically from the equivalent model as stability boundary of the multi-infeed HVDC system. The EESCR is also compared with other indices proposed recently to clarify their empirical or heuristic assumptions. The CEESCR stability boundary for a practical multi-infeed configuration is derived and verified by time-domain simulations to demonstrate the validity of the theoretical developments.
机译:本文推导了多馈入高压直流输电系统的等效单馈模型,为定义等效等效短路比(EESCR)的指标提供了理论依据,该指标可以解决应用有效短路时的歧义单馈至多馈HVDC系统的比率(ESCR)概念。此外,从等效模型中分析得出临界EESCR,作为多馈HVDC系统的稳定边界。还将EESCR与最近提出的其他指数进行比较,以阐明其经验或启发式假设。通过时域仿真推导并验证了实际多馈电配置的CEESCR稳定性边界,以证明理论发展的有效性。